IT
ALIANO
ENGLISH
6
IOMMASGPXX00-GB_01
Green Power
100-120 kVA
2.1 IMPORTANT.
• This document provides important instructions for the safe use, movement and connection of the MASTERYS™
uninterruptible power system (UPS).
• SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize
the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All
reproduction, modifi cation, dissemination of this document whether in part or whole and by any manner are
expressly prohibited except upon Socomec’s express prior written consent.
• This document is not a specifi cation. SOCOMEC UPS reserves the right to make any changes to data without prior
notice.
• The unit must be installed and activated only by qualifi ed technical personnel and authorised by SOCOMEC UPS.
The UPS MUST be handled with the utmost care by at least two people.
• The unit must remain in a vertical position in all circumstances.
• Connect the PE ground conductor fi rst before you make any other connection.
The UPS mains power supplies (rectifi er and bypass) must be protected from voltage transients
with devices that are suited to the installation; the mains voltage transients must be limited to 2.5
kV. These devices must be sized to take into account all the installation parameters (geographical
position, whether or not there is a lightning rod, whether or not there are other suppressors in the
electrical installation, etc.).
• Do not expose the UPS to rain or liquids in general. Do not introduce external bodies.
• If the UPS is not equipped with automatic sectioning against back feed or if the switch is external to the UPS, affi x
a label bearing the following words on all the external switches of the UPS power supply:
ISOLATE THE UPS BEFORE
OPERATING ON THIS CIRCUIT
• Keep this manual handy for future consultation.
• If the unit fails, it must be repaired only by authorised technicians that have been specially trained for this purpose.
• This equipment conforms to the European Community directives for professional equipment and bears the
approval mark
• The UPS requires three-phase plus neutral input connections (3P+N).
• The UPS can be supplied by an IT distribution system with a neutral conductor.
The connecting bars are made of aluminium!
Use only aluminium cables or cables with tinned eyelets for the connections.
• Do not connect the output neutral to ground. The UPS does not modify the neutral arrangements of the system;
SAFETY
2
Содержание Green Power 100
Страница 1: ...INSTALLATION AND OPERATING MANUAL Green Power 100 120 kVA ...
Страница 2: ......
Страница 42: ...ITALIANO ENGLISH 42 IOMMASGPXX00 GB_01 Green Power 100 120 kVA MIMIC PANEL 6 6 4 1 6 6 4 1 8 6 4 1 7 6 4 1 9 ...
Страница 64: ...FRANÇAIS ...