ENGLISH
IOMMASGPXX00-GB_01
57
Green Power
100-120 kVA
10
OPTIONS
10.1-1
OUT2
OUT3
IN1
IN3
OUT1
OUT4
IN1
IN2
DIP SWITCH 1
DIP SWITCH 1
DIP SWITCH 2
DIP SWITCH 2
10.1 ADC CARD.
This card can be confi gured to control up to four out-
puts that are normally closed or normally open
and up to three digital inputs. A maximum of
two cards can be installed on each unit.
Up to four operating modes can be select-
ed using the two DIP switches.
1. The filter level indicates:
-
1
immediate activation (1 seconds minimum communication time)
-
2
delay 10 s
2. If the external E.S.D. button is not used, always insert a jumper to short circuit
input In1.
POWER SAFE confi guration
IN/OUT
In1
2
In2
In3
Out1
Out2
Out3
Out4
Description
E.S.D
Supply from GenSet.
Management of energy
consumption
General Alarm
Power safe plug 1
Power safe plug 2
Power safe plug 3
Filter level
1
1
1
1
2
2
2
2
Position
dip1 dip2
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
SAFETY confi guration
IN/OUT
In1
2
In2
In3
Out1
Out2
Out3
Out4
Description
E.S.D
External alarm A39
Isolation controller
General Alarm
E.S.D. activation
Battery low and
imminent stop
E.S.D. activation
Filter level
1
1
2
2
2
1
2
1
Position
dip1 dip2
OFF ON
OFF ON
OFF ON
OFF ON
OFF ON
OFF ON
OFF ON
ENVIRONMENTAL confi guration
IN/OUT
In1
2
In2
In3
Out1
Out2
Out3
Out4
Description
E.S.D
External alarm A39
External alarm A40
General Alarm
Over-heating
Overload /
Loss of redundancy
External alarm In2
Filter level
1
1
2
2
2
2
2
2
Position
dip1 dip2
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
Содержание Green Power 100