22
IOMMASGPXX00-GB_01
Green Power
100-120 kVA
4
UNPACKING AND INSTALLATION
4.4.5 Connecting THE EXTERNAL BACKFEED PROTECTION.
To guarantee maximum protection, use a 220-240 V release
coil with integrated travel limit contact to pilot the input pro-
tection systems(see section 3.4 “Electrical requirements”).
If a trip coil without an integrated end-of-travel contact
is used, add an early auxiliary contact as shown in fi gure
4.4.5-1.
Electrical data of the contacts: 2 A 250 Vac
4.4.5-2a
F
ACS
B.K.
B.K.
XB1
B.K.
XB7
F1
VS1
NA1
COM1
XB8
NA2
COM2
XB9
F
N
230 V
BYPASS
B.K.
INPUT
XB4
XB2
XB3
BYPASS
INPUT
XB5
XB6
N
F2
VS2
4.4.5-3a
F
ACS
B.K.
B.K.
XB1
XB7
F1
NA1
COM1
XB8
NA2
B.K.
BYPASS
XB4
BYPASS
INPUT
N
F N
F N
VS2
Legend.
A
Distribution panel
B
Trip
coil
X10
Mains terminal board
X40
Aux Mains terminal board
MAINS
Mains
switch
AUX MAINS
Aux Mains switch
XB5
Aux Mains BKF connector
XB6
Mains BKF connector
AUX MAINS
AUX MAINS
protection
protection
MAINS
MAINS
protection
protection
Activating UPS protection on the mimic panel: access
the
Confi guration
menu on the mimic panel (see
the
Confi guration
Menu section in the manual) and
set the
BACKFEED TYPE
parameter to
2.BYPASS-INPUT
Alone
.
4.4.5-4a
A
UPS
AUX MAINS
X40
BKF
XB6
XB5
MAINS
B
B
X10
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
• Separate Mains.
4.4.5-1
B
L1
L2
L3
XB5 - XB6
N