Liebert® MicroPOD™ 120V

Installer/User Guide

Содержание Liebert MicroPOD

Страница 1: ...Liebert MicroPOD 120V Installer User Guide...

Страница 2: ...any installation or operational issues with your product check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures Visit https www VertivCo com e...

Страница 3: ...Installation 10 5 Startup Procedure 12 5 1 Electrical Connections 12 5 2 Pluggable Connections 12 5 3 Hardwire Connections 13 6 Indicator Lamps 16 6 1 Utility Indicator Lamp 16 6 2 UPS Indicator Lamp...

Страница 4: ...vacuum cleaners or electric drills into the UPS output receptacles WARNING Do not modify the cables in any way Consult your local Emerson representative if the AC cords do not match the utility recep...

Страница 5: ...ARNING When the Liebert MicroPOD is in Utility position maintenance bypass mode the power to the connected load is not filtered or conditioned by the UPS Vertiv Liebert MicroPOD Installer User Guide 5...

Страница 6: ...onal information Utility lamp indicates local power is available and the load may be transferred to bypass the UPS UPS lamp indicates UPS power is available and the load may be transferred to the UPS...

Страница 7: ...TILITY maintenance bypass In UPS mode the power is routed through the UPS system delivering conditioned power to the load as shown in Figure 2 1 below Figure 2 1 UPS mode of operation In Utility mode...

Страница 8: ...Figure 2 3 Liebert MicroPOD connections Vertiv Liebert MicroPOD Installer User Guide 8...

Страница 9: ...type of configuration 4 If you already have a UPS installed turn off all connected loads and unplug them from the UPS Turn off the UPS and disconnect the input cord 5 Attach the two Liebert MicroPOD s...

Страница 10: ...ng on your application utilizing the rack mount brackets provided 4 Determine the desired position and direction for the Liebert MicroPOD face it in that direction then attach the brackets to the Lieb...

Страница 11: ...OD mounting bracket location CAUTION Before installing open all branch rated circuit breakers at the nearest disconnect turn UPS off and disconnect all cords to and from the UPS Vertiv Liebert MicroPO...

Страница 12: ...on Plug the Liebert MicroPOD input cord labeled UTILITY into the utility outlet wall receptacle WARNING The Liebert MicroPOD is now electrically live The Utility lamp amber should be illuminated 2 Plu...

Страница 13: ...lectrical noise Conduit used alone without a grounding conductor wire is not an acceptable connection Size ground protective earth conductors equal in size to circuit conductors Wiring Instructions 1...

Страница 14: ...V Table 2 1 Breaker specifications To make the hardwire connections 1 Remove the wiring access doors by removing the two Phillips head screws that secure them 2 Determine which of the two available co...

Страница 15: ...anual 10 Verify that the UPS lamp green on the Liebert MicroPOD is illuminated If so transfer the rotary switch from UTILITY to UPS The load is now being supplied with conditioned power through the UP...

Страница 16: ...h If utility power is not present this lamp will be off and the UPS will supply battery backup power to connected loads 6 2 UPS Indicator Lamp This green lamp is illuminated when output power is avail...

Страница 17: ...cables connecting the UPS to the Liebert MicroPOD 5 You may now service the UPS 7 2 Transfer to UPS To transfer to UPS from maintenance bypass utility use the following steps 1 Reconnect the UPS to t...

Страница 18: ...d 10 ft 3m cord L5 30P on attached 10 ft 3m cord Connection to UPS Input 5 15R 5 15 20R T type L5 30R L5 30R L5 30R Connection to UPS Output 5 15P on attached 6 ft 1 8m cord 5 20 P on attached 6 ft 1...

Страница 19: ...dels MODEL POWER DISTRIBUTION BOX MODEL MP2 115HW MP2 120HW MP2 130HW USED WITH LIEBERT GXT RATING VA 500 1500 2000 3000 Dimensions W x D x H in mm Unit 15 51 x 3 03 x 3 46 394 x 77 x 88 Shipping 18 5...

Страница 20: ...ert MicroPOD units pluggable and hardwire This Liebert MicroPOD is intended for use with a UPS meeting all the following requirements UPS input cord is compatible with the rating and type of receptacl...

Страница 21: ...urn on UPS Refer to UPS user manual UPS input and or output cord not connected to Liebert MicroPOD Refer to Liebert MicroPOD installation instructions in this manual Installation on a Liebert GXT UPS...

Страница 22: ...Vertiv Liebert MicroPOD Installer User Guide 22...