MODEL
VA-VOLT
RATING
INPUT
CURRENT
RATING AT 120V
RECOMMENDED
(MAXIMUM)
EXTERNAL
OVERCURRENT
PROTECTION
RECOMMENDED
WIRE SIZE, AWG (MM2)
(INCLUDING
GROUND WIRE)
(75° COPPER WIRE)
MAXIMUM WIRE
ACCEPTED BY
TERMINAL
BLOCK
AWG (MM2)
TERMINAL
TIGHTENING
TORQUE
IN-LB (NM)
MP2-115HW
12A
15A
14 (2.08)
8 (8.36)
12 (1.3)
MP2-120HW
16A
20A
12 (3.31)
8 (8.36)
12 (1.3)
MP2-130HW
24A
30A
10 (5.26)
8 (8.36)
12 (1.3)
MP2-220N
15A*
20A
12 (3.31)
8 (8.36)
12 (1.3)
*The rated input current rating is at 208V.
Table 2.1 Breaker specifications
To make the hardwire connections:
1.
Remove the wiring access doors by removing the two Phillips head screws that secure them.
2. Determine which of the two available conduit entry points are to be used. Knock out the
conduit entry hole for the location and size of conduit to be used.
3. Connect conduit bushing and conduit and run utility load wiring.
4. Inspect wiring to ensure it is not pinched.
5. Make connections to the terminal blocks as labeled.
6. Reattach the wiring access doors and reinstall the retaining screws.
Figure 2.6 Removing plates to make hardwire connections
Vertiv
| Liebert® MicroPOD ™ Installer/User Guide |
14
Содержание Liebert MicroPOD
Страница 1: ...Liebert MicroPOD 120V Installer User Guide...
Страница 8: ...Figure 2 3 Liebert MicroPOD connections Vertiv Liebert MicroPOD Installer User Guide 8...
Страница 22: ...Vertiv Liebert MicroPOD Installer User Guide 22...
Страница 24: ...Vertiv Liebert MicroPOD Installer User Guide 24 This page intentionally left blank...
Страница 25: ......