If you have chosen a manual address conflict resolution ("PUSH BUTTON"), there will be one or several conflicts if multiple
devices have the same Modbus address.
A pop-up message will be displayed on the HMI:
AUTODETECT
.
|
ADDRESS CONFLICTS DETECTED!
PRESS THE AUTOADDRESS BUTTON ON
ALL NON-BLINKING DEVICES TO SOLVE THE
CONFLICTS.
To manually resolve address conflicts, locate the devices which have a lit and stable "COM" LED. Press and hold down
the addr. button on the front face of the module for about 2 seconds until the LED flashes:
Press
2 sec.
Press
2 sec.
COM LED ON AND STABLE = address conflict
COM LED FLASHING = product address identified correctly.
AUTODETECT
.
|
STATUS
STOPPED
FOUND / CONFLICT
004 / 000
DIGIWARE ADDRESSING RANGE
001:247
METHOD
FAST
START
The number of detected products increases and the number of conflicts decreases to reach zero once all products have a
unique address.