8.2. Automatic detection of slave devices
The auto-discovery function scans and discovers slave devices connected to the Digiware and RS485 buses and
automatically assigns a unique Modbus address to each device.
The auto-discovery function is compatible with DIRIS Digiware modules, DIRIS B and DIRIS A-40 power meters.
For other devices such as COUNTIS energy meters and DIRIS A-10/A-20/A-30/A-60 power meters, you must change
their Modbus address manually.
Example of auto-discovery on a D-50/D-70 display.
Four products are connected to the D-50 / D-70. Two are addressed correctly, the other two have an identical address.
Digiware bus
U-30
@3
I-30
@4
I-30
@5
I-30
@5
D-50 / D-70
@2
Go to “PARAMETERS” / “AUTODETECT SERIAL DEVICES”:
PARAMETERS
|
DISPLAY
CONFIGURE A DEVICE
AUTODETECT SERIAL DEVICES
LIST PRODUCTS
ADD NEW DEVICE
…
Click on “DIGIWARE ADDRESSING RANGE”:
AUTODETECT
.
|
STATUS
STOPPED
FOUND / CONFLICT
000 / 000
DIGIWARE ADDRESSING RANGE
001:247
METHOD
FAST
START