35
EN
DIRIS Digiware D-50 & D-70 - 548088B - SOCOMEC
10. WEBSERVER EMBEDDED IN THE D-50/D-70 DISPLAYS
A webserver is embedded for the configuration of network parameters (WEB-CONFIG, D-50/D-70) and the remote
visualisation of measurement data (WEBVIEW-M, D-70 only).
To connect to the gateway’s webserver, enter its IP address in the address bar of your web browser.
Default Ethernet parameters of the DIRIS Digiware D-50/D-70 displays are as follows:
- IP address: 192.168.0.4
- Mask: 255.255.255.0
- Gateway: 192.168.0.1
10.1.
User profiles
Several profiles are available:
- User (default)
- Advanced User
- Administrator
- Cyber security
The Advanced User, Administrator and Cyber security profiles are authorised to modify settings.
PROFILE
ACCESS
DEFAULT PASSWORD
User
- Visualisation of measurement data
- Access to diagnostics
None
Advanced User
- Visualisation of measurement data
- Access to diagnostics
+ Password management of the Advanced User profile
+ Reset of counters
Advanced
Admin
- Visualisation of measurement data
- Access to diagnostics
+ Password management of the Admin profile
+ Access to configuration menu
Admin
Cyber security
- Visualisation of measurement data
- Access to diagnostics
- Password management of all profiles
- Access to configuration menu
+ Cyber Security configuration menu
+ Firmware upgrade via web server
Cyber