69
EN
DIRIS Digiware D-50 & D-70 - 548088B - SOCOMEC
Annex III - 3.
Understanding the exported .csv file in EMS mode
The csv file is split into two parts:
•
The part (1) in red corresponds to the header. It contains a unique key, created out of multiple parameters such as the
the site and server name, the data type, the data ID, the device ID to uniquely identify each parameter that is exported.
•
The part (2) in green contains the logged and time stamped measurements. Each line is identified via the simplified
index key, which refers to a unique key in cells B5 through B10.
The final value for cells C13 through C26 is obtained considering the right coefficient in cells G5 through G10 along with
the right unit in cells H5 through H10.
Example for line 13:
The final value for THD I1 of circuit PC1-2-3 on module I-35@4 is equal to 2.34 % on January 18th, 2019 at 15:14:00.
When integrating data into a third-party energy management or monitoring software, always refer to the unique Key in
column “B”, part (1) as a unique import code and do not only use the simplified index key in column “A”, part (2).
If multiple DIRIS Digiware D-70 displays are exporting to the same folder, the simplified index key cannot
differentiate them.