22
EN
DIRIS Digiware D-50 & D-70 - 548088B - SOCOMEC
This allows you to allocate Modbus addresses to the connected devices within a specific range:
AUTODETECT
.
|
START ADDRESS
001
END ADDRESS
247
NB ADDR. POSSIBLE
032
ADDR. SET METHOD
AUTO SET
APPLY SETTINGS
Choose the conflict resolution method (“ADDR. SET METHOD”):
- “PUSH BUTTON”: you must press the push button on each module to resolve address conflicts. The order you
will use to press the push buttons on the modules will also determine the order for the Modbus addressing of
those modules.
- “AUTOSET”: connected devices are automatically allocated individual Modbus addresses within the specified
range.
Click on “APPLY SETTINGS” to apply your modifications.
Choose the auto-discovery “METHOD”:
AUTODETECT
.
|
STATUS
STOPPED
FOUND / CONFLICT
000 / 000
DIGIWARE ADDRESSING RANGE
001:247
METHOD
FAST
START
- FAST (default mode): this mode will only detect DIRIS Digiware modules on the Digiware bus and RS485 bus,
DIRIS B and DIRIS A-40 on the RS485 bus.
- FULL: this mode will also detect other Socomec PMDs (DIRIS A) and meters (COUNTIS E) connected on the
RS485 bus.
Click on "START" then "OK" to start the auto-discovery process (this can take up to 5 minutes).
AUTODETECT
.
|
STATUS
STOPPED
FOUND / CONFLICT
000 / 000
DIGIWARE ADDRESSING RANGE
001:247
METHOD
FAST
START