9
EN
DIRIS Digiware D-50 & D-70 - 548088B - SOCOMEC
5.2.2.
Introduction to DIRIS Digiware D-70
The DIRIS Digiware D-70 display embeds a web-based software (WEBVIEW-M) which allows a remote visualisation of
real-time and historical measurements.
The DIRIS Digiware D-70 display is a master on the Digiware bus and acts as a gateway interface to communicate
measurements over RS485 and Ethernet.
The RS485 port can be configured as a Master or Slave.
The Ethernet port is used to:
•
Communicate via Modbus TCP (max. 16 simultaneous connections), measurements from meters and measuring
devices connected to the Digiware and RS485 buses.
•
Communicate via BACnet IP and SNMP, measurements from meters and measuring devices connected to the
Digiware and RS485 buses.
•
Automatically send alarm notifications via emails (SMTPS).
•
Synchronize the date/time to an SNTP server.
•
Automatically and cyclically export historical measurements via FTPS.
Data logging capabilities of the DIRIS Digiware D-70 are explained in the table below:
CONSUMPTION CURVES
LOAD CURVES
TRENDS
Logged data
Energy: kWh, kvarh, kVAh
Power: kW, kvar, kVA
Average measurements:
U, V, I, P, Q, S, PF,
Temperature...
Compatible products
COUNTIS Exx (all)
DIRIS Axx (all)
DIRIS Bxx (all)
DIRIS Digiware XXX (all)
Countis Eci, Countis E3x
DIRIS A-30 + MEM /
A60
DIRIS B-30
DIRIS Digiware I-31 /
I-61 /I-35 / I-45 / I-35dc /
S-135 / S-Datacenter
DIRIS A-40
DIRIS B-30
DIRIS Digiware I-35 / I-45 /
U-30 / U-31dc / U-32dc /
S-135 / S-Datacenter
DIRIS A-40
Integration period
configurable from Easy Config
System, 10 min to 60 min
configurable from Easy Config System,
1 min to 60 min
Data logging duration
1 year with a 60-min integration period.
Proportional for different values:
For example: 3 months with a 15-min integration period.
This applies no matter how many devices (1 to 32) are connected to the D-70. The level of
detail of the log is not linked to the number of devices connected:
Operation
Readings taken every 10 min /
60 min in the meter/PMD.
The data is recorded in a cache memory on the meter
and then downloaded by the D-70. If communication
is interrupted, the missing data is recovered by the
D-70 once the connection is restored so that recording
continues.
Data backup (in the event
of a loss of communication
between the D-70 and the
meter)
NO
YES (in the meter’s cache memory)
Export to FTP server
YES
YES
YES
Webview link
Specific configuration
Nothing to configure (data is
recorded automatically).
Load curves must be
activated on the meters (via
Easy Config System).
Load curves are then
automatically downloaded
from the meter’s cache
memory to the D-70.
Trends must be activated on
the meters (via Easy Config
System).
The logs are then
automatically downloaded
from the meter’s cache
memory to the D-70.