-32-
No.PF
※※
-OMX0002
■
Default setting
Function (Main display)
Default Settings
(Right sub display)
Applicable
Page
(Main display)
(Left sub display)
[F 0]
[rEF ] Select display units
[ Std] Standard condition
[Unit] Units selection function
1
[ L] L/min
[NorP] Select NPN/PNP
[ PnP] PNP output
[F 1]
[oUt1] Select output mode
[ HYS] Hysteresis mode
[1ot ] Select switch mode
[ 1_P] Normal output
[P_1 ] Select input switch operation
[1500] 1500 L/min (PF3A703H)
[3000] 3000 L/min (PF3A706H)
[6000] 6000 L/min (PF3A712H)
[H_1 ] Setting of Hysteresis
[ 150] 150 L/min (PF3A703H)
[ 300] 300 L/min (PF3A706H)
[ 600] 600 L/min (PF3A712H)
[dt1 ] Delay time setting
[0.00] 0.00 s
[CoL ] Select display colour
[1SoG] Green when ON
Red when OFF (OUT1)
[F 2]
[oUt2] Select output mode
[ HYS] Hysteresis mode
2
[2ot ] Select switch mode
[ 2_P] Normal output
[P_2 ] Select input switch operation
[1500] 1500 L/min (PF3A703H)
[3000] 3000 L/min (PF3A706H)
[6000] 6000 L/min (PF3A712H)
[H_2 ] Setting of Hysteresis
[ 150] 150 L/min (PF3A703H)
[ 300] 300 L/min (PF3A706H)
[ 600] 600 L/min (PF3A712H)
[dt2 ] Delay time setting
[0.00] 0.00 s
[CoL ] Select display colour
[1SoG] Green when ON
Red when OFF (OUT1)
[F 3]
[FiL ] Select digital filter
[ 1.0] 1 second
[F 5]
[FUnC] Select FUNC
(switching analogue output/external input)
3
[AoUt] Analogue output
[F10]
[SUb ] Select sub display (Line name setting
4
)
[ dEF] Default setting
[F13]
[rEv ] Select Reverse display
[ oFF] Reverse display OFF
[F14]
[CUt ] Select Zero cut-off setting
[ 1.0] 1%F.S. cut
[F30]
[SAvE] Accumulated value hold
[ oFF] Not stored
[F80]
[diSP] Display OFF mode
[ on] Display ON
[F81]
[Pin ] Security code
[ oFF] Not used
[F90]
[ALL ] Setting of all functions
[ oFF] Not used
[F96]
[S_in] Check of input signal
[ - - - ] No input signal
[F98]
[tESt] Setting of output check
[ n] Normal output
[F99]
[ini ] Reset to the default settings
[ oFF] Not used
1: Setting is only possible for models with the units selection function.
2: [F 2] The OUT2 setting can be set on the product screen, but since there is no OUT2 switch output function as an output
specification, it is not possible to output the ON/OFF signal to an external device.
3: When the 1 switch output type (output specification symbol is L) is used, [F5] is displayed as [---] and cannot be set.
1 to 5 V or 0 to 10 V can be selected when the analogue voltage output type is used.
Analogue output free range function can be selected.
4: When Line name is selected, a suitable line name can be input.