PDU-ATS-100A-208Y.120-3PH

100-amp Automatic Transfer Switch

208Y/120 3PH - Aluminum - NEMA 3R

Instruction Manual

Thank you for your purchase of the Larson Electronics

:

PDU-ATS-100A-208Y.120-3PH, 100-amp Automatic Transfer Switch

WARNING: 

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. 

CRITICAL SAFETY INSTRUCTIONS: 

INSTALLATION SHOULD ONLY BE CONDUCTED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NEC AND ANY

RELEVANT LOCAL BUILDING CODES.

RISK OF FIRE OR ELECTRIC SHOCK. FIXTURE INSTALLATION REQUIRES KNOWLEDGE OF ELECTRICAL

 

SYSTEMS. IF

NOT QUALIFIED, CONTACT A QUALIFIED ELECTRICIAN.

BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.

MAKE SURE THE SUPPLY VOLTAGE IS THE SAME AS THE RATED FIXTURES VOLTAGE.

TO PREVENT WIRING DAMAGE OR ABRASION, DO NOT EXPOSE WIRING TO EDGES OF SHEET METAL OR SHARP

OBJECTS. SUITABLE FOR DAMP LOCATIONS.

The standard switch enclosure is a National Electrical Manufacturer’s Association (NEMA) and UL 3R type. UL and NEMA 3R type 

enclosures primarily provide a degree of protection against falling rain and sleet; undamaged by the formation of ice on the enclosure.

Before installing, operating or servicing this equip-ment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all 

SAFETY RULES to prevent accidents and/or damage to the equip-ment. The manufacturer recommends a copy of the SAFETY 

RULES are made and posted near the trans-fer switch. Also, be sure to read all instructions and information found on tags, labels and 

decals affixed to the equipment.

The Larson Electronics PDU-ATS-100A-208Y.120-3PH Automatic Transfer Switch is ideal for managing electrical loads between two 

sources in industrial facilities. This 100-amp, 208Y/120 three-phase controller handles timing, sensing, exercise functions and transfer 

commands. Constructed of aluminum, the unit is housed in a NEMA 3R enclosure.

MOUNTING

PDU-ATS-100A-208Y.120-3PH

 

are wall-mounted or surface-mounted. Install the transfer switch as close as possible to 

the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent 

switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit.

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

1

 of 

13

 

3-POLE-MECHANISM

These switches (Figure 

1

) are used with a three phase system, 

when the three phase NEUTRAL line is to be connected to a 

NEUTRAL lug and is not to be switched.

Solderless, screw-type terminal lugs are standard. 
The conductor size range is as follows:

Switch Rating 

Wire Range

100 A 

#6-2/0 AWG

200A

#4-400 MCM 

Conductor sizes must be adequate to handle the max-imum current to 

which they will be subjected; based on the 75°C column of tables, 

charts, etc. used to size conductors. The installation must comply fully 

with all applicable codes, standards and regulations.

Содержание PDU-ATS-100A-208Y.120-3PH

Страница 1: ...anufacturer recommends a copy of the SAFETY RULES are made and posted near the trans fer switch Also be sure to read all instructions and information found on tags labels and decals affixed to the equipment The Larson Electronics PDU ATS 100A 208Y 120 3PH Automatic Transfer Switch is ideal for managing electrical loads between two sources in industrial facilities This 100 amp 208Y 120 three phase ...

Страница 2: ...0A 208Y 120 3PH Larson Electronics LLC Phone 800 369 6671 Fax 903 498 3364 www larsonelectronics com 2 of 13 POWER PDU ATS 100A 208Y 120 3PH is compatible with input voltages of 208Y 120 3PH Power source and load connec tions are made at a transfer mechanism inside the switch enclosure Before connecting wiring cables to terminals remove any surface oxides from the cable ends with a wire brush All ...

Страница 3: ...o utility termi nals N1 N2 N3 o UTILITY window A OFF STANDBY window ON LOAD termi nals T1 T2 T3 are connected to emergency terminals E1 E2 E3 Larson Electronics LLC Phone 800 369 6671 Fax 903 498 3364 www larsonelectronics com 3 of 13 PDU ATS 100A 208Y 120 3PH CLOSE TO NORMAL SOURCE SIDE Before proceeding verify the position of the switch by observing THE UTILITY window If window reads ON the cont...

Страница 4: ...SED position 4 With an accurate AC voltmeter and frequency meter check the no load voltage and frequency Measure across ATS terminal lugs E1 to E2 E2 to E3 and E1 to E3 Measure across ATS terminal lugs E1 to NEUTRAL E2 to NEUTRAL and E3 to NEUTRAL a Frequency 60 62 Hz b Terminals E1 E2 E2 E3 E1 E3 208 212VAC or 470 485 c Terminals E1 N E2 N E3 N 120 122VAC or 272 282 d It will also be necessary to...

Страница 5: ...ter than 59 Hz c Let the generator run under rated load for at least 30 minutes With unit running listen for unusual noises vibration overheating etc that might indicate a problem 5 When checkout under load is complete set main circuit breaker of the generator to the OFF or OPEN position 6 Let the generator run at no load for several minutes Then shut down by setting the AUTO OFF MANUAL switch to ...

Страница 6: ...arsonelectronics com 6 of 13 Section 5 Mounting Dimensions RTS W Type Transfer Switch Mounting Dimensions 100 200A 208V 513 04mm 20 2 613mm 24 1 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 179 5mm 7 1 490mm 19 3 61 5mm 2 4 41 5mm 1 6 MOUNTING HOLES Ø6 35mm Ø0 25 4 PLACES 430mm 16 9 ...

Страница 7: ...w larsonelectronics com 7 of 13 Section 5 Mounting Dimensions RTS W Type Transfer Switch Mounting Dimensions 100A 480V 609 6mm 24 0 917mm 36 1 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 254mm 10 0 794mm 31 3 60 8mm 2 4 61 3mm 2 4 487mm 19 2 MOUNTING HOLES Ø6 35mm Ø0 25 4 PLACES ...

Страница 8: ...larsonelectronics com 8 of 13 332mm 13 1 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 1220 9mm 48 1 1092mm 43 0 63 5mm 2 5 765 8mm 30 1 65 39mm 2 6 MOUNTING HOLES Ø6 35mm Ø0 25 4 PLACES 635mm 25 0 Section 5 Mounting Dimensions RTS W Type Transfer Switch Mounting Dimensions 200A 480V ...

Страница 9: ...ND NOTE SINGLE PHASE UTILITY SUPPLY FROM SERVICE DISCONNECT 23 USED ON 3 PHASE SYSTEMS NOTE E3 N3 AND T3 WIRES ARE ONLY NOTE 178 AND 183 APPLICATION NOT USED IN THIS CONNECTIONS ARE 194 E CONNECTION WIRE 178 CUST T OMER 8 7 NEUTRAL BLOCK CONNECTION PANEL QT SERIES ENGINE GENERATOR E1 N1 E2 E3 ON 3 PHASE E1 E2 T3 T2 T1 0F4034 CUSTOMER LOAD DISTRIBUTION PANEL WIRE WIRE N1 N2 WIRE WIRE 057329 T NEUTR...

Страница 10: ...23 194 23 194 N2A LEGEND GTS NOTES 1 ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY POSITION B A WHITE RED LS2 LS3 LS1 T1 T2 2 3 5 6 1 4 3 4 5 N1B N2A N3 PM N1B N1A PM F2 N2 N1 F1 N1B N2A 126 C CONTACTOR ACTUATING COIL GTS TRANSFER SWITCH CONTACTOR PM POWER MONITOR 3 PHASE UTILITY TR RELAY TRANSFER TS TERMINAL STRIP CUSTOMER CONNECTION LS1 LS2 LS3 LIMIT SWITCHES ACTUATOR F1 F2 FUSE 5A SENSING ...

Страница 11: ...W Type Transfer Switch Wiring Diagram Schematic 100 200A 208V TR GTS T1 E1 N1 T2 E2 N2 B1 B2 A2 A1 N1B N1B 126 E2 E1 N2A 205 N1B 205 E1 E1 A 7 1 B 9 3 6 T1 T2 N1B N2A N3 E3 T3 2 1 8 7 3 4 5 6 126 205 N2A N2A N2A N1B N1B N1B N1B N1A N3 PM N3 N3 N1B N1B F2 F1 23 194 TS UTILITY 2 UTILITY 1 N2A N2A N2A N3 N3 N3 194 23 23 194 23 194 N1 N2 N2A N2A N2A N2A ...

Страница 12: ...S NOTES 1 ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY POSITION B A RED LS2 LS3 LS1 T1 T2 2 3 5 6 1 4 3 4 5 N2A N3 PM N1B PM F2 N2 N1 F1 N2B 126 1 8 TR1 240V X4 X1 OR 600V H4 480V H1 H1 X4 240V X1 H4 480V OR 600V TR2 N1C N2B N2B N2B 23 194 E1 E2 ATS TRANSFER SWITCH CONTACTOR C CONTACTOR ACTUATING COIL PM POWER MONITOR 3 PHASE UTILITY TR RELAY TRANSFER TS TERMINAL STRIP CUSTOMER CONNECTION LS...

Страница 13: ...1 B 9 3 T1 T2 N3 E3 T3 2 1 8 7 3 4 5 6 PM F2 F1 H4 X4 X1 H1 H4 X4 X1 H1 UTILITY 1 UTILITY 2 1 TB 2 3 4 23 194 5 Z Y NB N2B 205 E2A 126 N2B N3 N2A N1A E1A N1A N2A E2A E2 E1 N3 N3 194 E1A 23 205 N2 N1 23 194 E1 E2 N2A N1A N1A N2A N1A N2A E2A N3 N1C N1C N1C N2B N2B N2B N1B N1B N1B N1B N1B Section 6 Electrical Data RTS W Type Transfer Switch Wiring Diagram Schematic 100 200A 480V ...

Страница 14: ...ed modification may impair the function and or safety of this device and could affect the life of the equipment Always check for damaged or worn out parts before using the device Store it in a secure place out of the reach of children when not in use Inspect for good working condition prior to storage and before re use REPLACEMENT PARTS The PDU ATS 100A 208Y 120 3PH is designed to provide years of...

Отзывы: