[F 5] FUNC setting
Analogue output or external input can be selected.
•When analogue output is selected
1 to 5 V or 0 to 10 V can be selected when the analogue voltage output type is used.
The flow value corresponding to 5 V (10 V) or 20 mA can be selected with the analogue output free range
function.
•When external input is selected
The Accumulated Flow, Peak Value and Bottom Value can be reset remotely.
•Accumulated Flow External Reset: A function to reset the Accumulated Flow value when an external input
signal is applied.
In accumulated increment mode, the accumulated flow value will reset
to zero, and then increase from zero.
In accumulated decrement mode, the accumulated flow value will reset
to a set value, and then decrease from the set value.
: When the Accumulated Value is memorized, every time the Accumulated Value External Reset is activated, the memory will be
accessed. Take into consideration the maximum number of times the memory can be accessed is 1.5 million times. The total of
External Input times and Accumulated Value Memorizing time interval should not exceed 1.5 million times.
•Peak/ Bottom value reset: A function to clear the peak value or bottom value when an external input signal
is applied.