-90-
No.PF
※※
-OMX0002
Specifications
Models
PF3A703H
PF3A706H
PF3A712H
Fluid
Applicable fluid
1
Air, N
2
Operating fluid temperature
0 to 50
o
C
Flow
specifications
Detection method
Heating type sensor
Rated flow range
30 to 3000 L/min
60 to 6000 L/min
120 to 12000 L/min
Set point
range
Instantaneous
flow
30 to 3150 L/min
60 to 6300 L/min
120 to 12600 L/min
Accumulated
flow
0 to 999,999,999,990 L
0 to 999,999,999,900 L
Minimum
resolution
Instantaneous
flow
2 L/min
5 L/min
10 L/min
Accumulated
flow
10 L
100 L
Accumulated volume per
pulse
(Pulse width = 50 msec.)
Select from 100 L/pulse and 1000 L/pulse
Accumulated value hold
2
2 minutes or 5 minutes
Pressure
specifications
Rated pressure range
0.1 to 1.5 MPa
Proof pressure
2.25 MPa
Pressure loss
Refer to the pressure loss graph
Pressure Characteristics
3
±2.5%F.S. (0.1 to 1.0 MPa, 0.5 MPa standard)
Electrical
specifications
Power
supply
voltage
Used as switch
output device
24 VDC ±10%
Used as
IO-Link device
18 to 30 VDC ±10%
Current consumption
150 mA or less
Protection
Polarity protection
Accuracy
Display accuracy
±3.0%F.S.
Analogue output accuracy
±3.0%F.S.
Repeatability
Display, switch output, analogue output: ±1.0%F.S.
Temperature characteristics
±5.0%F.S. (Ambient temp. 0 to 50
o
C, 25
o
C standard)
Switch output
Output type
Select from NPN or PNP open collector output
Output mode
Selects one of the output (hysteresis or window comparator mode),
the output for the accumulated flow, the accumulated pulse output,
error output and switch OFF.
Switch operation
Normal or reversed output
Maximum load current
80 mA
Maximum applied voltage
(Only NPN)
30 VDC
Internal voltage drop
(Residual voltage)
1.5 V or less (Load current 80 mA)
Delay time
4
3.3 ms or less
Variable at 0 to 60 s/0.01 step
Hysteresis
5
Variable
Protection
Over current protection