Process data
Process data is the data which is exchanged periodically between the master and device.
This product process data consists of switch output status, error diagnostics, fixed output and flow
measurement value.
(Refer to the table below.)
Bit offset
Item
Notes
0
OUT1 output
0: OFF 1: ON
1
OUT2 output
0: OFF 1: ON
8
Measurement diagnostics
0: Within range 1: Out of range (HHH)
14
Fixed output
0: Normal output 1: Fixed output (Setting of output check)
15
Error Diagnosis
0: Error not generated 1: Error generated
16 to 31
Flow measurement value
With sign: 16 bit
Bit offset
31
30
29 28 27 26 25
24
23 22 21 20 19 18
17
16
Item
Flow measurement value (PD)
Bit offset
15
14
13 12 11 10 9
8
7
6
5
4
3
2
1
0
Item
Error
diagnosis
Fixed
output
Reservation
Flow
diagnosis
Reservation
OUT2
OUT1
Switch output
•The process data of this product is Big-Endian type.
When the transmission method of the upper communication is Little-Endian, the byte order will be
changed.
Refer to the table below for the Endian type of the major upper communication.
Endian type
Upper communication protocol
Big-Endian type
Such as PROFIBUS and PROFINET
Little-Endian type
Such as EtherNET/IP, EtherCAT and CC-Link IE Field.