HRX-OM-M091
Chapter 2 Contact input/output communication
2.5 Contact input signal
HRS Series
2-16
2.5 Contact
input
signal
There are two contact input signals. As the default condition, contact input
signal 1 is used for run/stop signal (signal type: alternate), and contact input
signal 2 is not used. The input signals can be customized depending on the
customer’s application.
Table 2.5-1
Contact input signal
Class of signal
Signal configuration
Timer
Description
Display
Description
Display
Delay
timer of
reading
OFF
detection
Default
setting
Alternate ALT -
-
○
Run/stop
signal
RUN
Momentary MT
-
-
External switch
signal input
(N.O)
SW_A Alternate ALT Used Used
External switch
signal input
(N.C)
SW_B Alternate ALT Used Used
Contact input
signal 1
Without intput
signal
OFF
-
-
- -
Alternate ALT -
-
Run/stop
signal
RUN
Momentary MT
-
-
External switch
signal input
(N.O)
SW_A Alternate ALT Used Used
External switch
signal input
(N.C)
SW_B Alternate ALT Used Used
Alternate ALT -
-
Remote signal
RMT
Momentary MT
-
-
Contact input
signal 2
Without input
signal
OFF
-
-
- -
○
2.5.1 Run/stop
signal
・
Remote signal
1) Run/stop signal (Signal type: Alternate)
The product keeps operating while the input signal from the customer is ON.
OFF
ON
Run
Stop
Product condition
Run/stop signal
(
Alternate
)
2) Run/stop signal (Signal type: Momentary)
The state changes when the input signal from the customer goes OFF. This signal operates while
the product is stopped, and stops while the product is being operated. Maintain the ON condition
for 300ms or longer.
OFF
ON
Run
Stop
Product condition
Run/stop signal
(
Momentary
)
300ms
300ms