HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series
5.2 Communication specification
5-3
5.2 Communication
specification
Table 5.2-1
Communication specification of simple communication protocol
Item
Specification
Standard
Select from
EIA RS-485/RS-232C
Communication speed
Select from 1200bps/2400bps/4800bps/9600bps/19200bps
Data
・
bit length
Select from 7bit/8bit
Stop
・
bit length
Select from 1bit
、
2bit
Parity
Select from without parity ,odd number ,even number
Letter code
ASCII mode
Slave address set range
Select from 1 to 99
Response delay time setting
Select from 0 to 250[msec]
Communication range
RO(Can read data only),
Select from RW(can read and write data)
BCC
Select from with BCC , without BCC
Error check
EXOR algorithm of all data from STX to ETX is read only when BCC
is selected.
:
Default setting