Chapter 2 Contact input/output communication
HRS Series
2.4 Setting and checking
2-11
22.
Select contact output signal 1 operation from the table below with [
▲
] key or [
▼
] key, and
confirm by pressing “SEL”.
Table 2.4-12
List of set values
Set values
Explanation
Initial value
(Default setting)
N.O type
○
N.C type
Contact output 1 selected alarm
Setting and checking
23.
Press the [SEL] key once.
The set screen of digital output 1 selected alarm
is displayed on the digital display.
PV
SV
24.
Select contact output 1 selected alarm from the table below with [
▲
] key or [
▼
] key, and
confirm by pressing “SEL”.
Table 2.4-13
List of set values
Set values
Explanation
Initial value
(Default setting)
Setting/checking are not available unless the
function setting of contact output 1 is selected
alarm status signal.
to
Sets selection alarm.
Set range is AL.01 to AL.36.
Contact output 2 function
Setting and checking
25.
Press the [SEL] key once.
The set screen of contact output 2 function is displayed on the digital display.
PV
SV