HRX-OM-M091
Chapter 5 Simple communication protocol function
5.5 Message configuration
HRS Series
5-14
The communication example is expressed in hexadecimal value with
[ ]. The actual communication is performed with ASCII co
de.
Refer to
the request / response message in this section
.
5.5.2 Message
example
The example shows communication with the conditions below.
○
Slave Address
:
No.1
○
Read seven consecutive data from register 0000h
.
(Read circulating fluid discharge temperature.)
Communication example
Request message
Response message
Code
Contents
Code
Contents
01
Slave Address
01
Slave Address
R
Request message to read
[ACK]
Normal response message
PV1
Circulating fluid discharge temperature
PV1
Circulating fluid discharge temperature
[65h] BCC
value
00187
Read information
[0Fh]
BCC
value
Request message (Master to Slave)
STX
Slave
Address
Request Command ETX
BCC
02 30 31 52 50 56
31
03
65
Response message (Slave to Master)
STX
Slave
Address
ACK Command
Reading
data
ETX
BCC
02 30 31 06 50 56
31
30 30 31 38 37 03 0F
This product
(Request): [STX] 01RPV1 [ETX] [65h]
(Response):
[STX] 01[ACK] PV100187 [ETX] [0Fh]
Your system
Data is sent and
received in ASCII
code.