HRX-OM-M091
Chapter 5 Simple communication protocol function
5.8 Command explanation
HRS Series
5-18
5.8.3
Command:SV1 Circulating fluid set temperature (W)
Read the circulating fluid set temperature in the selected temperature unit
(°C or °F).
Request message <Normal> (Master to Slave)
STX Slave
Address Request
Command
Writing
data
ETX BCC
[STX]
XX
XX
[W] [S] [V] [1]
XX
XX
XX
XX
XX
[ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave
Address ACK ETX BCC
[STX]
XX
XX
[ACK] [ETX]
XX
Communication example
○
Slave Address
:
No 1
○
BCC selection
Request message
Response message
Code
Contents
Code
Contents
01
Slave Address
01
Slave Address
W
Request message to write
[ACK]
Normal response message
SV1
Circulating fluid set temperature
[06h]
BCC value
00258
Write information (25.8
o
C)
[5Ch] BCC
value
Your system
This product
(Request)[STX] 01WSV100258 [ETX] [5Ch]
(Response)[STX] 01[ACK] [ETX] [06h]
Data is sent and
received in ASCII
code.
Содержание HRS012-W