HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series
5.8 Command explanation
5-21
5.8.6
Command:STR Saves data (W)
Store the circulating fluid set temperature set in 5.8.3 ‘’Command:SV1
Circulating fluid set temperature’’. Key-lock set data which is set in 5.8.5
‘’Command:LOC Key-lock setting (W)’’ is not the object to store.
Request message <Normal> (Master to Slave)
STX Slave
Address Request
Command ETX
BCC
[STX]
XX
XX
[W] [S]
[T] [R]
[ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave
Address ACK ETX BCC
[STX]
XX
XX
[ACK]
[ETX]
XX
Communication example
○
Slave Address
:
No 1
○
BCC selection
Request message
Response message
Code
Contents
Code
Contents
01
Slave Address
01
Slave Address
W
Request message to write
[ACK]
Normal response message
STR Saves
data
[06h]
BCC
value
[02h] BCC
value
Your system
This product
(Response)
[
STX
]
01
[
ACK][ETX][06h]
(Request)
[
STX
]
01WSTR[ETX][02h]
Data is sent and
received in ASCII
code.