HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking
HRS Series
2-4
2.4 Setting and checking
2.4.1
Setting and checking
The table below explains the setting items of the contact input/output signal
and the initial values.
Table 2.4-1
List of set communication items
Display
Item
Contents
Initial value
(Default setting)
Communication mode
Sets communication mode of this product.
LOC
Contact input signal 1
Setting contact input signal 1 of the contact
input/output communication.
RUN
Contact input signal 1 type
Setting input type of contact input signal 1 of the
contact input/output communication. [----] is
displayed when the setting of contact input signal 1 is
OFF.
ALT
Contact input signal 1 delay
timer of reading
Sets the delay timer of reading of contact input signal
1 of the contact input/output communication. Used
when the setting of the contact input signal 1 is
SW_A or SW_B. [----] is displayed when the setting of
the contact input signal 1 is not SW_A or SW_B.
-
Contact input signal 1 OFF
Detection timer
Sets the OFF detection timer of contact input signal 1
of the contact input/output communication. Used
when the setting of the contact input signal 1 is
SW_A or SW_B. [----] is displayed when the setting of
the contact input signal 1 is not SW_A or SW_B.
-
Contact input signal 2
Setting contact input signal 2 of the contact
input/output communication.
OFF
Contact input signal 2 type
Setting input type of contact input signal 2 of the
contact input/output communication. [----] is
displayed when the setting of contact input signal 2 is
OFF.
ALT
Contact input signal 2 delay
timer of reading
Sets the delay timer of reading of contact input signal
2 of the contact input/output communication. Used
when the setting of the contact input signal 2 is
SW_A or SW_B [----] is displayed when the setting of
the contact input signal 2 is not SW_A or SW_B.
-
Contact input signal 2 OFF
Detection timer
Sets the OFF detection timer of contact input signal 2
of the contact input/output communication. Used
when the setting of the contact input signal 2 is
SW_A or SW_B. [----] is displayed when the setting of
the contact input signal 2 is not SW_A or SW_B.
-
Contact output 1 function
Setting output signal function of contact output 1 of
the contact input/output communication.
RUN
Contact output 1 operation
Setting output signal operation of contact output 1 of
the contact input/output communication.
A
Contact output 1 selected
alarm
Setting selected alarm of contact output 1 of the
contact input/output communication. [----] is
displayed when the setting of the output signal of
contact output1 is not selected alarm signal.
AL.01
Contact output 2 function
Setting output signal function of contact output 2 of
the contact input/output communication.
RMT
Contact output 2 operation
Setting output signal operation of contact output 2 of
the contact input/output communication.
A
Contact output 2 selected
alarm
Setting selected alarm of contact output 2 of the
contact input/output communication. [----] is
displayed when the setting of the output signal of
contact output2 is not selected alarm signal.
AL.01
Contact output 3 function
Setting output signal function of contact output 3 of
the contact input/output communication.
ALM
Contact output 3 operation
Setting output signal operation of contact output 3 of
the contact input/output communication.
B
Contact output 3 selected
alarm
Setting selected alarm of contact output 3 of the
contact input/output communication. [----] is
displayed when the setting of the output signal of
contact output3 is not selected alarm signal.
AL.01