HRX-OM-M091
Chapter 2 Contact input/output communication
2.2 Communication specification
HRS Series
2-2
2.2 Communication
specification
Table 2.2-1
DIO Communication specification
Item
Specification
Connector type (for this product) MC
1,5/12-GF-3,5
Insulation system
Photo coupler
Rated input voltage
DC24V
Used input voltage
DC 21.6V to 26.4V
Rated input current
5mA TYP
Contact input
signal
Input signal
4.7k
Ω
Rated load voltage
AC48V or less/DC30V or less
Contact output
signal
Maximum load current
AC/DC 500mA (Resistance load)
Output voltage
DC24V±10
%
0.5A MAX
2.3 Terminal block explanation
This part explains the terminal block of the contact input/output
communication. A communication cable that connects the product and
customer system is not included with the product. Prepare a cable, referring
to Table 2.3-1 and Fig 2.3-1. Use the connector included as an accessory.
Table 2.3-1
Terminal explanation
Terminal
no
Application
Division
Default setting
Setting
available
1
Common of contact output signal 3
2
Contact output signal 3
Output
Alarm signal
(
N.C type
)
○
3
Common of contact output signal 2
4
Contact output signal 2
Output
Remote signal
(
N.O type
)
○
5
Common of contact output signal 1
6
Contact output signal 1
Output
Run status signal
(
N.O type
)
○
7
Common of contact input signal 2
8
Contact input signal 2
Input None
○
9
Common of contact input signal 1
10
Contact input signal 1
Input
Run/stop signal
(
Alternate
)
○
11
24V COM output
Output
12
DC 24V output
Output