HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 59 of 77
9 PARAMETERS SETTING
In HGM9310MPU(CAN) controller, there are no items of mains in setting and also no mains
items in configurable ports of input/output.
CAUTION:
Please change the controller parameters when generator is in standby mode
only (e. g. Crank disconnect conditions selection, auxiliary input, auxiliary output, various
delay), otherwise, shutdown and other abnormal conditions may happen.
NOTE:
Maximum set value must over minimum set value in case that the condition of too
high as well as too low will happen.
NOTE:
When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value must less
than set value; When setting the minimum value, the return value must over set value.
NOTE:
Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as crank disconnect.
NOTE:
Auxiliary input could not be set as same items; otherwise, there are abnormal
functions. However, the auxiliary output can be set as same items.