HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 57 of 77
8.4 SELECTION OF SENSORS
Form4
No.
Description
Remark
1
Temperature
Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
5 VOLVO-EC
6 DATCON
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
Defined resistance’s
range
is
(0~6)
KΩ,
default is SGX
sensor.
2
Pressure Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS
5 VOLVO-EC
6 DATCON 10Bar
7 SGX
8 SGD
9 SGH
10 VDO 5Bar
11 DATCON 5Bar
12 DATCON 7Bar
13~15 Reserved
Defined resistance’s
range
is
(0~6)
KΩ,
default is SGX
sensor.
3
Oil Level Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 SGD
4 SGH
5~15 Reserved
Defined resistance’s
range is
(0~6)KΩ
,
default is SGH
sensor.
NOTE:
User should make special declare when order controller if your genset equip
with sensor of 4~20mA.