HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 55 of 77
when input is active.
11
Inhibit Scheduled Run
In
Auto
mode, inhibit scheduled run genset when
input is active.
12
Reserved
13
Aux Gen Closed
Connect generator loading switch’s Aux. Point.
14
Inhibit Gen Load
Prohibit genset switch on when input is active.
15
Aux Mains Closed
Connect mains loading switch’s Aux. Point.
16
Inhibit Mains Load
Prohibit mains switch on when input is active.
17
Auto Mode Lock
When input is active, controller enters into Auto
mode; all the keys except
are inactive.
18
Auto Mode Invalid
When input is active, controller won’t work under
Auto mode.
key and simulate auto key
input does not work.
19
Controller Backlit
The LCD backlight will illuminated when the input
is active.
20
Controller Buzzer
Controller buzzer will peal when the input is
active.
21
Inhibit Alarm Stop
All shutdown alarms are prohibited except
emergence stop.(Means battle mode or override
mode)
22
Aux Instrument Mode
All outputs are prohibited in this mode.
23
Reset Maintenance 1
Controller will set maintenance time and date 1 as
default when input is active.
24
Reset Maintenance 2
Controller will set maintenance time and date 2 as
default when input is active.
25
Reset Maintenance 3
Controller will set maintenance time and date 3 as
default when input is active.
26
Aux. High Temp
Connected sensor digital input.
27
Aux. Low OP
Connected sensor digital input.
28
Remote Start
(On Load)
In
Auto
mode, when input active, genset can be
started automatically and take load after genset
normal running; when input inactive, genset will
stop automatically.
29
Remote Start
(Off Load)
In
Auto
mode, when input is active, genset can be
started automatically and NOT take load after
genset normal running; when input is inactive,
genset will stop automatically.
30
Aux. Manual Start
In
Manual
mode, when input active, genset will