![Smartgen HGM 9310CAN Series Скачать руководство пользователя страница 72](http://html.mh-extra.com/html/smartgen/hgm-9310can-series/hgm-9310can-series_user-manual_1297502072.webp)
HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 72 of 77
15.11 MTU MDEC
Suitable for MTU engines, 2000 series, 4000series
Terminals of controller
X1 connector
Remark
Fuel relay output
BE1
Start relay output
BE9
CAN GND
E
CAN communication shielding
line(connect with one terminal
only)
CAN(H)
G
Impedance 120Ω connecting line
is recommended.
CAN(L)
F
Impedance 120Ω conn
ecting line
is recommended.
Engine type: MTU-MDEC-303
15.12 MTU ADEC(SMART MODULE)
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Terminals of controller
ADEC (X1port)
Remark
Fuel relay output
X1 10
X1 Terminal 9 Connected to
negative of battery
Start relay output
X1 34
X1 Terminal 33 Connected to
negative of battery
Terminals of controller
SMART (X4 port)
Remark
CAN GND
X4 3
CAN communication shielding
line(connect to controller’s this
terminal only)
CAN(H)
X4 1
I
mpedance 120Ω connecting line
is recommended.
CAN(L)
X4 2
Impedance 120Ω connecting line
is recommended.
Engine type: MTU-ADEC