HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 46 of 77
8.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS
Form 2
No.
Type
Description
0
Not Used
1
Custom Period 1
Details of function description please see the following.
2
Custom Period 2
3
Custom Period 3
4
Custom Period 4
5
Custom Period 5
6
Custom Period 6
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13
Reserved
14
Reserved
15
Gas Choke On
Action while cranking. Action time is as pre-seted.
16
Gas Ignition
Action when genset starting, and disconnect when
engine stopped.
17
Air Flap
Action when over speed shutdown and emergence stop.
It can close the air inflow to stop the engine as soon as
possible.
18
Audible Alarm
Action when warning, shutdown, trips. Can be
connected annunciator externally. When “alarm mute”
configurable input port is active, it can remove the
alarm.
19
Louver Control
Action when genset is cranking and disconnect when
genset stopped completely.
20
Fuel Pump Control
It is controlled by fuel pump of level sensor’s limited
threshold.
21
Heater Control
It is controlled by heating of temperature sensor’s
limited threshold.
22
Cooler Control
It is controlled by cooler of temperature sensor’s limited
threshold.
23
Oil Pre-supply Output
Action from “crank on” to “safety on”.
24
Excite Generator
Output in start period. If there is no generator frequency
during normal running, it outputs for 2 seconds again.
25
Pre-Lubricate
Actions in period of pre-heating to safety run.
26
Remote PC Output
This port is controlled by communication (PC).
27
GSM Power
Power for GSM module (GSM module is reset when
GSM communication failed).
28