![Smartgen HGM 9310CAN Series Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/smartgen/hgm-9310can-series/hgm-9310can-series_user-manual_1297502076.webp)
HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 76 of 77
15.19 YUCHAI
It is suitable for BOSCH common rail pump engine.
Terminals of controller
Engine 42 pins port
Remark
Fuel relay output
1.40
Connect to engine ignition lock
Start relay output
-
Connect to starter coil directly
CAN GND
-
CAN communication shielding
line(connect with controller’s this
terminal only)
CAN(H)
1.35
I
mpedance 120Ω connecting line is
recommended.
CAN(L)
1.34
Impedance 120Ω connecting line is
recommended.
Battery
Engine 2 pins
Remark
Battery negative
1
Wire diameter 2.5mm
2
Battery positive
2
Wire diameter 2.5mm
2
Engine type: BOSCH
15.20 WEICHAI
It is suitable for Weichai BOSCH common rail pump engine.
Terminals of controller
Engine port
Remark
Fuel relay output
1.40
Connect to engine ignition lock
Start relay output
1.61
CAN GND
-
CAN communication shielding
line(connect to the controller at this
end only)
CAN(H)
1.35
Impedance 120Ω connecting line is
recommended.
CAN(L)
1.34
Impedance 120Ω connecting line is
recommended.
Engine type: GTSC1
NOTE:
If there is any question of connection between controller and ECU
communication, please feel free to contact Smartgen’s service.