HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 42 of 77
No.
Items
Parameters
Defaults
Description
2
Module
Address
(1~254)
1
Controller’s address during remote
sensing.
3
Stop Bits
(0~1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0~2)
0
0: Simplified Chinese 1: English
2: Others
5
Password
(0~65535)
00318
For entering advanced parameters
setting.
6
Temperature
Units
(0-1)
0
0
:
°C
;
1
:
°F
7
Pressure Units
(0-2)
0
0
:
kPa; 1
:
Psi; 2
:
Bar.
8
Module Mute
(0-1)
0
0: Disable 1: Enable
9
User Page
(0-1)
0
0: Disable 1: Enable
10
User Page
Time
(0-20.0)s
3.0
If “User Page Time” is enabled, the
user-set time will be displayed
continuously.
11
Date and Time
Set the module’s date and time.
GSM Setting
1
GSM Enable
(0~1)
0
0: Disable; 1: Enable
2
Phone Number Max.20 digits
0
0: Disable; 1: Enable
Its national and area’s cods must be
added. e.g. China: 8613666666666.
Scheduling And Maintenance Setting
1
Scheduled Run (0~1)
0
0: Disable; 1: Enable
2
Scheduled Not
Run
(0~1)
0
0: Disable; 1: Enable
3
Maintenance
(0~1)
0
0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1
Curve Type
(0~15)
7
SGX See form 5.
2
Open Circuit
Action
(0~2)
0
0: Warn; 1: Shutdown;
2: No action
3
High
Temp.
Shutdown
(0~300)ºC
98
Shutdown when sensor temperature
higher than this value. Detecting only
after safety delay is over. The delay
value (default: 3s) can be set.
4
High
Temp.
Warn
(0~300) ºC
95
Warn when sensor temperature
higher than this value. Detecting
only after safety delay is over. The
delay value (default: 5s) and return
value (default: 93) can be set.
5
Low
Temp.
Warn
(0~1)
0
0: Disable; 1: Enable
Oil Pressure Sensor