HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 37 of 77
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
No.
Items
Parameters
Defaults
Description
Mains Setting
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Rated Voltage (30~30000)V
230
Standard for checking mains
over/under voltage. (It is primary
voltage when using voltage
transformer).
3
Rated
Frequency
(10.0~75.0) Hz 50.0
Standard for checking mains
over/under frequency.
4
Normal Time
(0~3600)s
10
The delay from mains abnormal to
normal.
5
Abnormal Time (0~3600)s
5
The delay from mains normal to
abnormal.
6
Volt.
Trans.(PT)
(0~1)
0
0: Disable ; 1: Enable
7
Over Voltage
(0~200)%
120%
Setting value is mains rated voltage’s
percentage, and return value (Over
Voltage default: 116; Under Voltage
default: 84) and delay value (default:
5s) can be set.
8
Under Voltage (0~200)%
80%
9
Over
Frequency
(0~200)%
114%
Setting value is mains rated
frequency’s percentage, return value
(Over Frequency default: 110; Under
Frequency default: 94) and delay
value (default: 5s) can be set.
10
Under
Frequency
(0~200)%
90%
11
Loss of Phase
(0~1)
1
0: Disable; 1: Enable
12
Reverse Phase (0~1)
1
Timer Setting
1
Start Delay
(0~3600)s
1
Time from mains abnormal or remote
start signal is active to start genset.
2
Return Delay
(0~3600)s
1
Time from mains normal or remote
start signal is deactivated to genset
stop.
3
Preheat Delay (0~3600)s
0
Time of pre-powering heat plug
before starter is powered up.
4
Cranking Time (3~60)s
8
Time of starter power up
5
Crank Rest
Time
(3~60)s
10
The waiting time before second
power up when engine start fail.