HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 18 of 77
Note:
1. Input active power: generator or mains supply electricity to load.
2. Output active power: load supply electricity to generator or mains.
3. Input reactive power: generator or mains send reactive power to load.
4. Output reactive power: load send reactive power to generator or mains.
Mains,
including as below,
Phase voltage, line voltage, frequency, phase sequence
NOTE: HGM9310MPU
,
HGM9310CAN has no mains status screen.
Alarm:
Display all alarm information. e.g. warning alarm, shutdown alarm, trip alarm and trip and stop
alarm.
NOTE:
For ECU alarms and shutdown alarms, if the alarm information is displayed,
check engine according to it, otherwise, please check the manual of generator according to
SPN alarm code.
Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or stop)
and the real time when alarm occurs.
Others,
including,
Time and Date, count down time for maintenance, input/output ports status
About,
including,
Issue time of software and hardware version, product PD number
Power
factor
Conditions
Active
power
Inactive power
Remark
COS>0L
P>0,Q>0
Input
Input
Load is inductive resistance.
COS>0C P>0,Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0,Q>0
Output
Input
Load equal to one under excitation
generator
COS<0C P<0,Q<0
Output
Output
Load equal to one over excitation
generator.