IMPORTANT INFORMATION ABOUT THESE INSTRUCTIONS
7
© SMA Solar Technology AG Subject to changes to the technical content! Version 1.1 Last updated 04/2021
1.5 Intended use
STORAGE-67-TS-10 is a modular battery storage system based on lithium-ion technology. The components
reflect the current state of the art and meet product-specific standards.
STORAGE-67-TS-10 is designed for operation with the 3-phase battery inverter Sunny Tripower Storage 60
(STPS 60-10) manufactured by SMA. Any other use must be approved by the manufacturer and, if necessary,
the local utility company.
The unit may be operated only in closed rooms. The STORAGE-67-TS-10 works in an ambient air temperature
range of -10 °C to 50 °C and at a maximum humidity of 85 %.
The battery cabinet must not be exposed to direct sunlight and must not be placed directly next to heat sources.
The battery cabinet must not be subjected to corrosive atmospheres.
When installing the battery storage system, ensure that it is standing on a sufficiently dry, horizontal and flat sur-
face with sufficient load-bearing capacity.
The battery cabinet may not be installed at a location more than 2,000 m above sea level without the written
approval of the manufacturer.
In areas prone to flooding, the battery cabinet must always be installed in an elevated location where it is pro-
tected from making contact with water.
Pursuant to IEC 62619, the storage system must be installed in a fire-proof room. This room must be fitted with an
independent fire alarm unit which complies with local regulations and standards and must be free of fire loads.
The room must be separated from other rooms by class T60 fire doors. Similar fire protection requirements also
apply to other openings in the room (e.g. windows).
Intended use also includes compliance with these instructions.
Essentially, the STORAGE-67-TS-10 may not be used:
•
for mobile use on land or in the air (it may only be used on water in agreement with and with the written con-
sent of the manufacturer).
•
for use with medical equipment
•
as a UPS system.
1.6 Requirements for installers
Local regulations and standards must be followed for any work carried out.
The battery storage system may only be installed by qualified electricians who have the following qualifications:
•
training in dealing with hazards and risks associated with the installation and operation of electrical devices,
systems and batteries,
•
training in the installation and commissioning of electrical devices,
•
knowledge of and adherence to the locally applicable technical connection requirements, standards, direc-
tives, regulations and laws,
•
knowledge of the proper handling of lithium-ion batteries (transport, storage, disposal, and sources of dan-
ger)
•
knowledge of and adherence to these installation and operating instructions as well as other applicable
documents.