2 Safety
The STORAGE-67-TS-10 meets the requirements of IEC 61508 parts 1 to 7 and complies with safety integrity
level (SIL) 1.
DANGER! Life-threatening electric shock from damaged components or short circuit
Bridging the battery poles causes a short circuit resulting in a flow of electrical current. A short circuit of this type
must be avoided under all circumstances. you should therefore observe the following points:
•
Use insulated tools and insulated gloves.
•
Do not place any tools or metal parts on the battery modules or the APU.
•
Always remove watches, rings and other metal objects when working with the batteries.
•
Never operate or install the battery system in explosive environments or areas with relatively high humidity.
•
Before beginning any work on the battery storage system, first switch off the charge controller and then dis-
connect the battery from the voltage supply and secure them from being switched on again.
DANGER!
Chemical burns and poisoning due to electrolyte or toxic gases
During normal operation, no electrolyte can leak from the battery and no toxic gases can form. Despite careful
design, damage to the battery in the event of an error can result in electrolyte leakage, or toxic gases, organic
solvent gases and hydrofluoric acid may form in small concentrations and quantities. The following instructions
must therefore be observed:
•
Do not subject the battery module to violent impacts.
•
Do not open, disassemble or tamper with the battery module.
In case of contact with electrolyte, immediately wash the affected area with water and seek medical advice
without delay.
DANGER!
Life-threatening burns as a result of improper handling
Improper handling can cause lithium battery cells to ignite. It is therefore essential that you observe the following
instructions for handling lithium battery cells:
•
Never install or operate the battery modules in potentially explosive environments or areas with relatively
high humidity levels.
•
The battery modules must be stored in a dry place and within the temperature ranges specified in the data
sheet.
•
Do not open, perforate or drop the battery cells or modules.
•
Do not expose the battery cells or modules to high temperatures.
•
Do not throw the battery cells or modules into a fire.
•
In the event of a fire originating from the battery, extinguish it with a CO
2
fire extinguisher. In the event of a
fire in the vicinity of the battery, use an ABC fire extinguisher.
•
Do not use defective or damaged battery modules.
DANGER! Risk of death due to misuse
Any use of the battery storage system beyond the intended use or any other type of use can result in consider-
able danger.
DANGER! Risk of death due to unqualified operation
Incorrect handling of the battery storage system can result in considerable danger to the operator. Any action
requiring the battery cabinet to be opened must therefore only be carried out by qualified personnel in accor-
dance with the instructions in section “1.6 Requirements for installers“ on page 7.