30
COMMISSIONING
© SMA Solar Technology AG Subject to changes to the technical content! Version 1.1 Last updated 04/2021
8 Commissioning
8.1 Commissioning of a single unit
ATTENTION! Risk of damage to the battery due to incorrect configuration.
Improper configuration can result in damage to the battery. The parameters settings affect the charging behavior
of the STPS 60-10. It is therefore important to set the parameters correctly during commissioning.
Requirements
The STPS 60-10 has been installed in accordance with the installation and connection specifications.
Procedure
1
Check the cabling of the STPS 60-10 and the STORAGE-67-TS-10 (also see the STPS 60-10 installation guide).
2
Check the cabling of the components in accordance with section ““5.5 Battery module wiring“ on page 17
et seq. If the cabling is correct, all live components will be protected against physical contact. Switch DC circuit
breaker in the BatBreaker (if applicable) to “ON.” Make sure that the STPS 60-10 DC load-break switch is set to
“ON.”
ATTENTION! Risk of damage to the APU due to undetected errors during installation.
Carry out the check carefully in accordance with step
2
, as deviations may damage the APU
.
ATTENTION! Risk of damage to the APU due to improper operation.
If you tap on the APU to activate it or confirm an action, be sure to comply with the following instructions to
avoid damaging the APU:
1 .
Do not use objects to tap on the unit under any circumstances.
2 .
Do not tap the casing too hard with your fingers to the right of the display at the
16
marking.
Never tap on
the display under any circumstances
.
3
Now commission the SMA Inverter Manager
12
.
4
Check and, if necessary, correct the settings for the termination and
addressing of the STORAGE-67-TS-10 (TERM
5
and
ADDRESS
10
). TERM must be set to “ON” when operating a single
STORAGE-67-TS-10 and ADDRESS must be set to “0” and “0.”
5
Press the on/off switch (SWITCH)
17
on the SMA HV APU.
6
The number of recognized battery modules (14 or 16) will be displayed
on the screen. Confirm the correct number by tapping the marking
16
next to the display twice. If the number of modules displayed differs
from the actual number, take the unit out of operation and check the
BAT COM cabling. If the error persists, please contact the service cen-
ter.
TERM
ON
OFF
ADRESS
BATTERY
CHARGER
ADDRESS