CONNECTION TO THE SUNNy TRIPOWER STORAGE 60
29
© SMA Solar Technology AG Subject to changes to the technical content! Version 1.1 Last updated 04/2021
7.2 Diagram of connections STPS 60-10
DANGER! Risk of lethal electric shock or damage to the unit due to incorrect connection.
The STPS 60-10 installation guide provides authoritative information for correctly connecting the STPS 60-10.
The information provided in the instructions before you are therefore not binding.
ATTENTION! Risk of damage to the unit if the installation requirements are not met.
Before connecting the STPS 60-10, the installation of the STORAGE-67-TS-10 must be completely finished.
ATTENTION! Possible system malfunction due to improper cable routing
Communication, measuring and control cables must always be routed separately from AC/DC cables, as elec-
tromagnetic coupling can otherwise cause interference during data transmission and consequently lead to sys-
tem malfunctions.
NOTE:
When using a BatBreaker
15
in master/slave systems, use the DC connector set
16
to connect the
BatBreaker to the STPS 60-10.
BATTERY
CHARGER
E
F
D
C
B
A
LAN 2
Switch
LAN 1
Switch
(Janitza UMG 604/605)
LCS tool
SMA Data Manager M
SMA
Inverter Manager
In master/slave systems, the DC connection
of the TS HV 70 goes to the SMA STPS 60 via a BatBreaker.
TS HV 70
SMA
STPS 60
BatBreaker
Master/slave systems
Power Measurement
ITEM DESIGNATION
DESCRIPTION
A
AC terminal clamps
The tightening torque must be 20 Nm for
conductor cross-sections of 35 to 95 mm²
and 30 Nm for conductor cross-sections of
96 to 150 mm².
Note: When using flexible or very flexible
cables, wire end ferrules must be used for
the connection.
25 –33 mm
Use Al/Cu 35 –150mm²
(2-300 MCM AWG)
for min. 75°C
230
mm
L1
L2
L3
PE
B
Unit ground
C
Protection against AC overvoltage
Surge Protection Device SPD
D
Protection against DC overvoltage
Surge Protection Device SPD
E
DC terminal clamps
On/off switch for the battery: The tightening
torque for a conductor cross-section of 35 to
50 mm² is: 20 Nm.
Note: When using flexible or very flexible
cables, wire end ferrules must be used for
the connection.
Use Al/Cu 35 –150mm²
(2-300 MCM AWG)
for min. 75°C
205
mm
L1
L3
25 –33 mm
F
Ethernet interface 2x
Communication interface to the SMA Inverter Manager
STOP