SIGLENT
124 SSG5000X Programming Guide
Default
0 mV
Menu
I/Q Control > I/Q Output > I Output Offset
Example
:DM:IQADjustment:EXTernal:DIOFfset 1
3.8.6.13
Q Output Offset
([:SOURce]:DM:IQADjustment:DQOFFset)
Command
Format
[:SOURce]:DM:IQADjustment:EXTernal:DQOFfset <val>
[:SOURce]:DM:IQADjustment:EXTernal:DQOFfset?
Instruction
This command sets the differential offset voltage for an a quadrature-
phase (Q) signal routed to the Q output connectors
Parameter
Type
Float
Parameter
Range
-3 V ~ 3 V
Return
Float
Default
0 mV
Menu
I/Q Control > I/Q Output > Q Output Offset
Example
:DM:IQADjustment:EXTernal:DQOFfset 1
3.8.6.14
I/Q Common Offset
([:SOURce]:DM:IQADjustment:EXTernal:COFFset)
Command
Format
[:SOURce]:DM:IQADjustment:EXTernal:COFFset <val>
[:SOURce]:DM:IQADjustment:EXTernal:COFFset?
Instruction
This command sets the common mode offset voltage for both the in-phase
(I) and quadrature-phase(Q) signals going to the rear panel I and Q output
connectors.
Parameter
Type
Float
Parameter
Range
-3 V ~ 3 V
Return
Float
Default
0 mV
Menu
I/Q Control > I/Q Output > I/Q Common Offset