Configuration
6.1 Basic knowledge for configuring
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
91
6.1.3.3
Cable feeder units
Application area
Supplying LX busbar trunking systems when only cable connection is possible.
Design
●
Rated currents from 800 A to 3200 A
●
Choice of desired incoming cable connection unit in accordance with selection lists
●
Incoming cable connection unit as delivered without joint block
●
Connection of the cable direct to the connecting bars of the incoming cable connection
unit (bolt connection) for connecting 4 to 8 multi-core or single-core cables.
Number of cables
Type of cable connection
4 multi-core or single-core cables (to
300 mm
2
)
LX.01...-KE. to LX.02...-KE.
6 multi-core or single-core cables (to
300 mm
2
)
LX.03...-KE. to LX.05...-KE.
8 multi-core or single-core cables (to
300 mm
2
)
LX.06...-KE. to LX.07...-KE.
●
3 system-independent enclosure sizes
Enclosure size
Type of cable connection
Enclosure size 1
LX.01...-KE. to LX.02...-KE.
Enclosure size 2
LX.03...-KE. to LX.05...-KE.
Enclosure size 3
LX.06...-KE. to LX.07...-KE.