Technical data
7.17 Fixing distances
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
155
7.17
Fixing distances
Fixing distances [m] for conventional mechanical load with horizontal installation
System
Edgewise busbars
Flat busbars
LXA(C)01..
2
2
LXA(C)02..
2
2
LXC03..
2
2
LXA(C)04..
2
2
LXA(C)05..
3
2
LXA(C)06..
3
2
LXA(C)07..
3
2
LXA(C)08..
3
2
LXA(C)09..
3
2
LXA10..
3
2
7.18
Connection units for non-Siemens distribution boards
The required conductor cross sections for bare copper bars for connection to connection
units for non-Siemens distribution boards.
Number ... Cu bar
width x thickness
System
I
e
[A]
1
2
3
4
Compatible LXA/LXC system
LXC(A)01.. 1000 (800)
1)
60 x 10
30 x 10
20 x 10
-
LXA01.. and LXC01..
LXC(A)02.. 1250 (1000)
1)
80 x 10
40 x 10
30 x 10
-
LXA02.. and LXC02..
LXC03..
1400
100 x 10
50 x 10
30 x 10
-
LXC03..
LXC(A)04.. 1600 (1250)
1)
100 x 10
60 x 10
30 x 10
-
LXA04.. and LXC04..
LXA05..
1600
100 x 10
60 x 10
30 x 10
-
LXA05..
LXC05..
2000
160 x 10
80 x 10
50 x 10
-
LXC05..
LXC(A)06.. 2500 (2000)
1)
200 x 10
100 x 10
60 x 10
50 x 10
LXC06.. and LXA06..
LXC(A)07.. 3200 (2500)
1)
-
160 x 10
100 x 10
80 x 10
LXC07.. and LXA07..
LXC(A)08.. 4000 (3200)
1)
-
200 x 10
120 x 10
100 x 10
2)
LXC08.. and LXA08..
LXC(A)09.. 5000 (4000)
1)
-
-
200 x 10
160 x 10
LXC09.. and LXA09..
LXA10..
4500
-
-
160 x 10
120 x 10
LXA10..
1)
Connection to LXA systems
2)
In accordance with DIN 43671, Table 1, the maximum continuous current for this copper
cross section is 3980 A.