Configuration
6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
115
Vertical busbar run layout between two junction units, Case 1
●
Always position the expansion compensation units in the centre between the fixed points.
)3
)3
'
)3
/
/
/
'
L1
Max. permissible sub-length
L
Total run length
D
Expansion compensation
FP Fixed point (type: LX-BVFP..)
EF End cap
Examples of power transmission with LXA...., (LXC....)
Run length L
[m]
Number of fixed points (FP)
Number of expansion
compensation units (D)
≤ 6 (≤ 6)
2
0
≤ 25 (≤ 40)
2
1
≤ 50 (≤ 80)
3
2
≤ 75 (≤ 120)
4
3
Examples of power distribution with LXA...., (LXC....)
Run length L
[m]
Number of fixed points (FP)
Number of expansion
compensation units (D)
≤ 6 (≤ 6)
2
0
≤ 50 (≤ 60)
2
1
≤ 100 (≤ 120)
3
2
≤ 150 (≤ 180)
4
4