Configuration
6.1 Basic knowledge for configuring
SIVACON 8PS - Configuring with LX system
86
Configuration Manual, 10/2011, A5E02194899-02
Phase sequence and phase distances
Three different types are available for configuring (distances specified in mm):
Type 1: LX...-AS1
●
All tag distances (L1, L2, L3, PEN(N)) are identical: min. 115 mm, max. 400 mm
●
The PEN(N) phase is always on the outside
Phase sequence
+LX-.A
L1
L2
L3
PEN(N)
+LX-.B
PEN(N)
L3
L2
L1
+LX-.C
L3
L2
L1
PEN(N)
+LX-.D
PEN(N)
L1
L2
L3
Tag distance (in mm)
PLQ
PD[
/;3
Example for complete order type with tag distance 350 mm:
LXA0541-AS1+LX-1C+LX-P350