Technical data
7.2 Trunking units LXA..30 (aluminium)
SIVACON 8PS - Configuring with LX system
126
Configuration Manual, 10/2011, A5E02194899-02
7.2
Trunking units LXA..30 (aluminium)
System-specific data
LXA
0130
0230
0430
0530
0630
Rated current
I
e
A
0800
1000
1250
1600
2000
Conductor impedance
Resistance
R
20
mΩ/m 0.117
0.084
0.056
0.036
0.027
Reactance
X
20
mΩ/m 0.028
0.031
0.024
0.017
0.009
At 50 Hz and + 20 °C
busbar temperature
Impedance
Z
20
mΩ/m 0.120
0.090
0.061
0.040
0.035
Resistance
R
1
mΩ/m 0.146
0.106
0.07
0.043
0.034
Reactance
X
1
mΩ/m 0.028
0.031
0.024
0.017
0.009
At 50 Hz and final heating
of busbars
Impedance
Z
1
mΩ/m 0.149
0.110
0.074
0.046
0.029
Resistance
R
F
mΩ/m 0.223
0.214
0.180
0.116
0.110
Reactance
X
F
mΩ/m 0.140
0.139
0.114
0.095
0.071
for 5-pole systems (PE)
under fault conditions
acc. to EN 60439-2
Impedance
Z
F
mΩ/m 0.263
0.255
0.213
0.150
0.131
Zero impedance
R
0
mΩ/m 0.434
0.473
0.428
0.275
0.277
X
0
mΩ/m 0.363
0.354
0.293
0.250
0.195
for 5-pole systems (PE)
acc. to DIN EN 60909-0 /
VDE 0102
Z
0
mΩ/m 0.566
0.591
0.519
0.372
0.338
Short-circuit rating
Rated short-time
withstand current
rms value t = 1 s
I
cw
kA
25
35
50
60
75
Rated peak withstand
current
Peak value
I
pk
kA
53
70
110
132
158
Conductor material
Aluminium
No. of busbars
3
3
3
3
3
Conductor cross section L1, L2, L3
A
mm
2
292
386
586
946
1192
Equivalent copper cross
section
PE = enclosure
A
mm
2
948
948
1018
1135
1348
Weights
kg/m
9.6
10.6
13.3
17.8
21.8
Содержание SIVACON 8PS
Страница 2: ......
Страница 206: ...Glossary SIVACON 8PS Configuring with LX system 204 Configuration Manual 10 2011 A5E02194899 02 ...
Страница 209: ......