Technical data
7.9 Trunking units LXC..41 (copper)
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
141
System-specific data
LXC
0641
0741
0841
0941
Rated current
I
e
A
2500
3200
5)
4000
5000
Conductor impedance
Resistance
R
20
mΩ/m 0.017
0.013
0.011
0.009
Reactance
X
20
mΩ/m 0.009
0.011
0.008
0.005
At 50 Hz and + 20 °C
busbar temperature
Impedance
Z
20
mΩ/m 0.019
0.017
0.014
0.010
Resistance
R
1
mΩ/m 0.021
0.016
0.014
0.011
Reactance
X
1
mΩ/m 0.009
0.011
0.008
0.005
At 50 Hz and final heating
of busbars
Impedance
Z
1
mΩ/m 0.022
0.020
0.016
0.012
Resistance
R
F
mΩ/m 0.032
0.024
0.021
0.018
Reactance
X
F
mΩ/m 0.033
0.037
0.029
0.018
for 5-pole systems (PE)
under fault conditions
acc. to EN 60439-2
Impedance
Z
F
mΩ/m 0.046
0.044
0.036
0.025
Zero impedance
R
0
mΩ/m 0.061
0.047
0.041
0.035
X
0
mΩ/m 0.046
0.049
0.043
0.026
for 5-pole systems (PE)
acc. to DIN EN 60909-0 /
VDE 0102
Z
0
mΩ/m 0.077
0.068
0.059
0.044
Short-circuit rating
Rated short-time
withstand current
rms value t = 1 s
I
cw
kA
86
100
150
150
Rated impulse withstand
current
Peak value
I
pk
kA
189
220
255
255
Conductor material
Copper
No. of busbars
4
4
8
8
Conductor cross section L1, L2, L3
A
mm
2
1192
1586
1892
2384
Equivalent copper cross
section
PEN
A
mm
2
2540
2934
4162
5080
Weights
kg/m
55.2
70.6
88.9
110.5
1)
Reduction in rated current to 800 A with horizontal flat mounting position
2)
Reduction in rated current to 1380 A with horizontal flat mounting position
3)
Reduction in rated current to 1570 A with horizontal flat mounting position
4)
Reduction in rated current to 1900 A with horizontal flat mounting position
5)
Reduction in rated current to 3100 A with horizontal flat mounting position
Содержание SIVACON 8PS
Страница 2: ......
Страница 206: ...Glossary SIVACON 8PS Configuring with LX system 204 Configuration Manual 10 2011 A5E02194899 02 ...
Страница 209: ......