Configuration
6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
104
Configuration Manual, 10/2011, A5E02194899-02
Load tap-off point from 800 A to 1,250 A
Load tap-off points from 800 A to 1,250 A can only be implemented for the system sizes
LXA(C)05..to LXA(C)10...
Size
Tap-off unit with circuit breaker Tap-off unit with fuse switch
disconnector
1
≤ 250 A
≤ 250 A
2
315 ... 630 A
400 A
3
—
630 A
4
800 ... 1250 A
—
①
Size 4 (800 A to 1250 A)
②
Straight length without tap-off points
Minimum length W
min
= 2000 mm
③
Tap-off joint block is used instead of the joint block on the trunking unit.
④