Commissioning
6.3 Application examples
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
61
①
Sensor reference point
⑥
A = 0.8 m
②
0.5 m
⑦
L = 6 m
③
High calibration point
⑧
100% = 8000 L
④
3.5. m
⑨
Volume reading
⑤
Low calibration point
Parameter type Parameter Name
Options/
Values
Function
Quick Start
Wizard parame-
ters
Introduction
NEXT
Continue with Wizard.
Language
NEXT
Continue with current language.
Material
LIQUID
Response Rate
MED
Medium =1 m/minute
Units
M
meters
Low Calibration Point
3.5
3.5 m (11.48 ft)
High Calibration Point
0.5
0.5 m (1.64 ft)
Wizard Complete
FINISH
Transfers Quick Start settings to
device.
Independent
parameters
Vessel Shape (2.4.1.1.)
PARABOLIC
ENDS
Defines vessel shape.
PV (volume/level) Units
(2.3.3.)
L
liters
Level Unit (2.3.2.)
M
meters
Maximum Volume (2.4.1.2.)
8000
8000 liters
Dimension A (2.4.1.3.)
0.8
0.8 m (2.62 ft)
Dimension L (2.4.1.4.)
6
6 m (19.68 ft)
Loss of Echo (LOE) Timer
(2.3.6.)
120
120 seconds
Return to
Measurement:
press
Mode
to start normal operation.
Содержание SITRANS L
Страница 258: ...LCD menu structure SITRANS LR250 with FOUNDATION FIELDBUS 258 Operating Instructions 09 2021 A5E32221411 AH ...
Страница 259: ...LCD menu structure SITRANS LR250 with FOUNDATION FIELDBUS Operating Instructions 09 2021 A5E32221411 AH 259 ...
Страница 260: ...LCD menu structure SITRANS LR250 with FOUNDATION FIELDBUS 260 Operating Instructions 09 2021 A5E32221411 AH ...