Parameter reference
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
141
①
Distance
②
High Calibration Point (process full level)
③
Sensor reference point
a)
④
Low Calibration Point (process empty level)
⑤
Level
a)
The point from which High and Low Calibration points are referenced: see Dimension
drawings (Page 185) and Threaded Horn Antenna with extension (Page 191).
Input Scaling (2.6.4.)
Lower Value (2.6.4.1.)
Defines the operational lower range value of the input value (Process Value Scale) in PV
(volume/level) Units. Process Value Scale normalizes the input value to a customer-defined
range.
Values
Range:
-999999
to
999999
Default: 0 %
Upper Value (2.6.4.2.)
Defines the operational upper range value of the input value (Process Value Scale) in PV
(volume/level) Units. Process Value Scale normalizes the input value to a customer-defined
range.
Values
Range:
-999999
to
999999
Default: 100 %