Parameter reference
SITRANS LR250 with FOUNDATION FIELDBUS
130
Operating Instructions, 09/2021, A5E32221411-AH
Example (values are for example purposes only)
Breakpoint Number
Level value (m)
Volume value (l)
1
0
0
2
5
500
3
9
3000
4
19.5
8000
Entering breakpoints via the hand-held programmer:
1.
The default for level values is percent: if you want to select units instead, navigate to
Setup
(2.) > Sensor (2.3.) > Level Unit (2.3.2.)
, and select the desired unit.
2.
Navigate to
Setup (2.) > Sensor (2.3.) > PV Units (volume/level) (2.3.3.)
, and select the
desired volume units.
3.
Go to
XY index (2.4.1.5.)
and enter the number of the breakpoint you wish to adjust: for
example, for breakpoint
1
enter
1
.
4.
Go to
X value (2.4.1.6.)
and enter the level value for the breakpoint just identified.
5.
Go to
Y value (2.4.1.7.)
and enter the volume value for the breakpoint just identified.
6.
Repeat steps 3 to 5 until values have been entered for all required breakpoints.
X value (2.4.1.6.)
See
XY Index (2.4.1.5.)
.
Y value (2.4.1.7.)
See
XY Index (2.4.1.5.)
.
Entering breakpoints via AMS:
See Linearization (LTB) (Page 79)
After completing the above steps you will need to configure AIFB 1 and/or AIFB 2. [See
AIFB 1
(2.6.)
and
AIFB 2 (2.7.)
for details.]
Signal Processing (2.5.)
In AMS Device Manager, see the General tab under Signal Processing (LTB) (Page 80).