Commissioning
6.3 Application examples
SITRANS LR250 with FOUNDATION FIELDBUS
60
Operating Instructions, 09/2021, A5E32221411-AH
Parameter
type
Parameter No. /Name
Options/
Values
Function
Quick Start
Wizard param-
eters
Introduction
NEXT
Continue with Wizard.
Language
NEXT
Continue with current
language.
Material
LIQUID
Response Rate
MED
Medium =1 m/minute
Units
M
meters
Low Calibration Point
5
5 m (16.4 ft)
High Calibration Point
0.5
0.5 m (1.64 ft)
Wizard Complete
FINISH
Transfers Quick Start
settings to device.
Independent
parameters
Loss of Echo (LOE) Timer (2.3.6.)
120
120 seconds
Return to
Measurement
: press
Mode
to start normal operation.
6.3.2
Horizontal vessel with volume measurement
Note
The minimum distance from the flange face to the target is limited by
Near Range (2.5.1.)
.
To obtain level measurement proportional to vessel volume in a chemical vessel:
•
Low Calibration Point = 3.5 m (11.48 ft) from sensor reference point
•
High Calibration Point = 0.5 m (1.64 ft) from sensor reference point
•
Max. fill/empty rate = 0.2 m/min (0.65 ft/min)
•
Select vessel shape, Parabolic Ends, and enter values for A and L, to obtain a volume
reading instead of level.
In the event of a loss of echo:
•
SITRANS LR250 is to report a status of BAD or UNCERTAIN after 120 seconds (2 minutes).