Parameter reference
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
125
Sensor Offset (2.3.7.3.)
A constant offset that can be added to or subtracted from the sensor value to compensate for
a shifted sensor reference point. (For example, when adding a thicker gasket or reducing the
standoff/nozzle height.) The units are defined in
Unit (2.3.1.)
.
Values
Range:
-99.999
to
99.999
Default: 0.000 m
Related Parameters
Unit (2.3.1.)
See
How the LTB works
: in manual
Foundation Fieldbus for Level Instruments
(7ML19985MP01)
for more details on sensor offset.
Low Level Point (2.3.7.4.)
The level when the material is at Low Calibration Point. The unit is defined in
Level Unit
(2.3.2.).
Values
Range:
-999999
to
999999
Default: 0%
High Level Point (2.3.7.5.)
The level when the material is at High Calibration Point. The unit is defined in
Level Unit
(2.3.2.).
Values
Range: -
999999
to +
999999
Default: 100%
Level Offset (2.3.7.6.)
A constant offset that can be added to Level. The unit is defined in
Level Unit (2.3.2.)
.
Values
Range:
-999999
to +
999999
Default: 0%
Rate (2.3.8.)
Response Rate (2.3.8.1.)
Sets the reaction speed of the device to measurement changes.
Note
Changing Response Rate resets
Fill Rate per Minute (2.3.8.2)
,
Empty rate per Minute
(2.3.8.3)
, and
Shots (2.5.6.)
.